Industrial combustion system
current location:Product Introduction
Two stage gas burner
product
ProductNews Center
newsThe two-stage gas burner has a gas controlled dual stage adjustment function and is a CE certified gas burner that complies with the European EN676 standard. The modulation function requires the installation of an automatic modulation device (kit needs to be ordered separately), with an adjustment ratio of 1:7.
The nitrogen oxide and carbon monoxide emissions of this combustion engine comply with the standards specified in European standard EN676 Class 3, with air conditioning on the combustion head. Equipped with butterfly shutter and combustion air clamp. Adjust the airflow manually, close the baffle to stop and prevent heat from spreading to the fireplace.
Easy to maintain, the mixing device can be removed without removing the burner from the boiler. The connecting flange of the power supply device. The two end open hinge facilitates the connection of the combustion head of the combustion engine, and the ignition combustion engine gas pipe group is equipped with operating and safety valves, pressure switches, pressure regulators, and gas filters for the gas pipeline.
The CE version of the gas pipe assembly includes operating valves and safety pneumatic drives, solenoid valve sealing control, pressure switches, pressure regulators, and gas filters. The connection between the gas pipeline and the incorrect test connector results in low air supply.
Use photoresistors to detect the presence of flames, control panel, and operation display diagram equipped with indicator lights. The terminal block is used for power supply and constant temperature supply of the combustion engine. The terminal block is controlled according to the second stage operation or used as a connection terminal block for electronic power. It is an electrical equipment with electronic protection level.
Characteristics of two-stage gas burner:
1. Adopting a fully enclosed fuel cycle system effectively saves energy and avoids safety issues related to fuel volatility, ensuring full and stable fuel combustion. Closing the baffle can prevent heat diffusion and save fuel.
2. The two-stage gas burner is equipped with an automation control system, which automatically controls the entire operation process and safety protection functions. The intelligent operation panel can display and adjust various values of the burner.
3. The two-stage gas burner has functions such as one key ignition, firepower control, operation monitoring, stability control, and flame monitoring. The equipment uses suction material devices to effectively reduce fan noise.
4. The electronic cam can adjust the air to gas ratio proportionally within the operating range according to the specific requirements of the boiler (optional automatic adjustment kit), with adjustment ratios of 1:5, 1:6, 1:10, depending on the model size.
5. The two-stage gas burner uses CE version gas pipe group, including operating valve and safety electromagnetic drive, gas filter, pressure switch and pressure regulator, to form a stable gas valve group.
6. The two-stage gas burner mixes air and gas for combustion, mixes them in the combustion head, and then adjusts the combustion air and combustion head to achieve efficient combustion. The two-stage gas burner is equipped with a butterfly door combustion air clamp for easy manual adjustment of air flow rate and air conditioning of the combustion head.
7. The integrated burner assembly has a lightweight structure, simple installation, easy maintenance, and can be connected and used on site.
8. When connecting the flange of the sliding boiler, it can quickly use the changes in boiler heat or various conflicts of the heat boiler. The open hinge at both ends facilitates the connection of the combustion head of the burner.
9. The two-stage gas burner has advantages such as automatic control operation, high thermal efficiency, energy conservation and environmental protection. It has been widely used in various industries such as industrial boilers, civil boilers, road construction machinery, petrochemicals, medical environmental protection, steel machinery, etc.
Product specifications:
Combustiblemethane
Pneumaticregulationforoperation
MINthermalpower(kW)1500
MAXthermalpower(kW)10850
MINflowrate(Sm3/H)159
MAXflowrate(Sm3/H)1148
PowersupplytypeAC
Numberofphases3N
Voltage(V)380
Currentfrequency(Hz)60
Fanenginepower(kW)22
Unpackagedweight(kg)573
Weightwithpackaging(kg)673
Width(mm)2610
Depth(mm)1760
Height(mm)1470